The family of SwitchsyncTM Controllers consists of
| SwitchsyncTM Controller | Main Application | Controls
Circuit Breaker Operation | Circuit Breaker Operation |
| E113 | Shunt Capacitor Banks,
Shunt Reactors | Open or Close | Three-pole |
| E213 | Shunt Capacitor Banks | Open and Close | Three-pole |
| F236 | Shunt Capacitor Banks,
Shunt Reactors,
Power Transformers | Open and Close | Single-pole |
| T183 | Power Transformers | Close | Single-pole |
| L183 | Uncompensated Transmission Lines | Close | Single-pole |
All controllers have provisions for adaptive input to compensate for systematic variations in operating time of the circuit breaker. In addition, Switchsync
TM F236, T183 and L183 have provisions for two external, predictive inputs (e.g. temperature variation, control voltage). These functions make it possible to achieve added precision in the timing of the controlled circuit breaker. They also have data memory that stores information on switching times, thus permitting condition monitoring of the circuit breaker.