ADVAC Ratings

ADVAC circuit breakers are available in continuous current ratings of 1200, 2000 and 3000 A rms.

Breaker TypeNom. Voltage Class kVRated Max. Voltage kVLow Freq. Withstand Voltage kVImpulse Level (BIL) kV CrestRated Short Circuit Current kA rmsShort Time Current kA rms 2 Sec.Close and Latch kA PeakRated Voltage Range Factor K
5ADV314.164.76196031.531.5821.0
5ADV404.164.76196040401041.0
5ADV504.164.76196050501301.0
7.5ADV407.28.25369540401041.0
15ADV2013.81536952020521.0
15ADV2513.81536952525651.0
15ADV3113.815369531.531.5821.0
15ADV4013.815369540401041.0
15ADV5013.815369550501301.0
ADVAC Notes:
1. The asymmetric capability ratio rating is 1.2.
2. Ratings are 50/60 Hz basis.
3. Higher dielectric ratings are available for most classes.