SACE Tmax

T5N 400 PR221DS-LS/I In=400 4p F F

 
 
 
 Loading Images..
General Information
Extended Product Type:
T5N 400 PR221DS-LS/I In=400 4p F F
Product ID:
1SDA054325R1
EAN:
8015644554200
Catalog Description:
C.BREAKER TMAX T5N 400 FIXED FOUR-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC PR221DS-LS/I R 400
Long Description:
C.BREAKER TMAX T5N 400 FIXED FOUR-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC PR221DS-LS/I R 400
Categories
    Products»
  • Low Voltage Products and Systems
  • »
  • Circuit Breakers
  • »
  • Molded Case Circuit Breakers
  • »
  • Tmax T
 
Ordering
EAN:
8015644554200
Minimum Order Quantity:
1 piece
Customs Tariff Number:
85362090
Dimensions
Product Net Width:
186 mm
Product Net Height:
205 mm
Product Net Depth:
103.5 mm
Product Net Weight:
6.25 kg
Container Information
Package Level 1 Units:
1 piece
Package Level 1 Width:
248 mm
Package Level 1 Height:
240 mm
Package Level 1 Length:
285 mm
Package Level 1 Gross Weight:
6.6 kg
Package Level 1 EAN:
8015644554200
Environmental
RoHS Status:
Planned to follow EU Directive 2002/95/EC August 18, 2005 and amendment after 2007-01-01
Additional Information
Electrical Durability:
7000 cycle
60 cycles per hour
IIT Publishing Status:
Level 0 - Information enabled
Mechanical Durability:
20000 cycle
120 cycles per hour
Number of Poles:
4
Power Loss:
Per Pole 16,5 W
Product Main Type:
SACE Tmax T
Product Name:
Automatic Circuit Breaker
Product Type:
CB
Rated Current (In):
400 A
Rated Impulse Withstand Voltage (Uimp):
8 kV
Rated Insulation Voltage (Ui):
1000 V
Rated Operational Voltage:
690 V AC
750 V DC
Rated Service Short-Circuit Breaking Capacity (Ics):
(220V AC) 70 kA
(230V AC) 70 kA
(380V AC) 36 kA
(400V AC) 36 kA
(415V AC) 36 kA
(440V AC) 30 kA
(500V AC) 25 kA
(690V AC) 20 kA
Rated Short-time Withstand Current (Icw):
for 1.0s 5 A
Rated Ultimate Short-Circuit Breaking Capacity (Icu):
(220V AC) 7 kA
(230V AC) 7 kA
(380V AC) 36 kA
(400V AC) 36 kA
(415V AC) 36 kA
(440V AC) 30 kA
(500V AC) 25 kA
(690V AC) 20 kA
(250V DC) 2 poles in series 36 kA
(250V DC) 3 poles in series 25 kA
(500V DC) 3 poles in series 16 kA
Rated Uninterrupted Current (Iu):
400 A
Release Type:
EL
Standards:
IEC 60947
Sub-type:
T5
Suitable For:
T5
Suitable for Product Class:
Moulded Case Circuit Breakers
Terminal Connection Type:
Fixed Circuit-Breakers
Test Voltage at Industrial Frequency for 1 Minute:
3500 V
Test Voltage Max (Utest):
3500 V
Version:
Fixed
Certificates and Declarations (Document Number)
Declaration of Conformity - CE:
RoHS Information:
Classifications
E-nummer:
3180377
ETIM 4.0:
EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 5.0:
EC000228 - Power circuit-breaker for trafo/generator/installation prot.
Object Classification Code:
Q
UNSPSC:
39121100
 Loading Images.. Close
3.10.0.53203

DOWNLOADS

Downloads

    •   Cancel
      • Twitter
      • Facebook
      • LinkedIn
      • Weibo
      • Print
      • Email
    •   Cancel

    Your preferences:

    ABB contact for United States of America

    seitp329 b33882d222a164a4c1257a9b0036a400