CPUs / Features
PM851PM856PM860PM861APM864APM865
Processor UnitPM851K01 incl:
1 PM851 CPU
and required
optional items
PM856K01 incl:
1 PM856 CPU
and required
optional items
PM860K01 incl:
1 PM860 CPU
and required
optional items
PM861AK01 incl:
1 PM861A CPU
and required
optional items
PM861AK02 incl:
2 PM861A CPUs
and required
optional items
PM864AK01 incl:
1 PM864A CPU
and required
optional items
PM864AK02 incl:
2 PM864A CPUs
and required
optional items
PM865AK01 incl:
1 PM865K01 CPU
and required
optional items
PM865AK02 incl:
2 PM865K02 CPUs
and required
optional items
High Integrity ControllerNoNoNoNoNoYes
Clock frequency24 MHz24 MHz48 MHz48 MHz96 MHz96 MHz
Memory (RAM)8 Mb8 Mb8 Mb16 Mb32 Mb32 Mb
CPU redundancy supportNoNoNoYesYesYes
Switch over time in red. conf. - - - max 10 msmax 10 msmax 10 ms
Ethernet channels122222
Performance,
1000 boolean operations
(a:=b and c)
0.46 ms0.46 ms0.23 ms0.23 ms0.15 ms0.15 ms
Comm. modules on CEX bus11212121212
I/O clusters on ModuleBus (local I/O)1 el. + 1 opt.1 el. + 7 opt.1 el. + 7 opt.1 el. + 7 opt.1 el. + 7 opt.1 el. + 7 opt.
I/O capacity on ModuleBus (local I/O)
(Non redundant confi guration only)
max 24 I/O
modules
max 96 I/O
modules
max 96 I/O
modules
max 96 I/O
modules
max 96 I/O
modules
Limited, see user
manual for details
Supported Communication modules
Profi busFoundation
Fieldbus
RS-232 CMB300INSUMDrivebusS100 I/O
interface
Genius
TRIO I/O
Satt I/O
ModuleCI854ACI860CI853CI855CI857CI858CI856CI862CI865
ProtocolDP-V1
(PA via
Linking
Device)
HSE
(H1 via
Linking
Device)
Modbus
master,
Comli
master/slave,
Siemens
master,
User defi ned
protocols
MB300IEEE 802.3ABB’s
Drivebus
ABB’s
S100 I/O
GeniusABB´s
Satt I/O
Master or slaveMasterMasterMaster/slaveMaster/slaveMasterMasterMasterMasterMaster
Number of channels112211 main, 2 aux111