The AC 800F hardware
The AC 800F has a modular structure. The CPU is designed as a backplane to which various modules – power supply units, Ethernet or fieldbus modules – can be attached in line with the application. On the fieldbus side, modules for PROFIBUS-DPV1, FOUNDATION Fieldbus HSE, MODBUS (master/slave, RTU or ASCII), IEC 608 0-5-101 and CAN for Freelance Rack I/O are available. The fieldbus line and the connected PROFIBUS slaves are entirely configured and parameterized using the Control Builder F engineering tool. No further external tools are needed for configuration. PROFIBUS slaves can be integrated into the system using a GSD) file or FDT/DTM). In the case of FOUNDATION Fieldbus, configuration takes place using CFF or DD files. This allows fieldbus parameterization even without connected field devices.
Also Freelance Rack I/O can be connected to the AC 800F, in which case a CAN module is used. This allows you to operate five I/O racks, with a total of around 1000 I/Os, for each AC 800F. The I/O racks are equipped with a link module and up to nine I/O modules and can be mounted separately at a distance of up to 400 m from the AC 800F.
Fieldbus modules
The AC 800F uses the fieldbus modules to collect and process real-time and diagnostic data. Up to four fieldbus modules can be mounted into one AC 800F.
The fieldbus modules have the following tasks and
characteristics:
• Electrical isolation between the process and system
• Status LEDs for the module status
• Independent fault detection and fault signaling
• Connection of the fieldbus lines
| Details of the fielbus modules |  |  |
| Type | Channels | Function |
| CAN module | 1 | Connection of up to 5 Freelance I/O racks |
 |  |  |
| Serial module |  | RS /RS4 /RS485 configurable for MODBUS, IEC 608 0-5-101 telecontrol protocol |
 |  |  |
| PROFIBUS module | 1 | Full-value PROFIBUS DPV1 Master |
 |  |  |
| FF-HSE module | 1 | For the connection of up to 10 LD 800HSE Linking Devices with 10/100 MBaud autosense twisted pair connection |
 |  |  |
Ethernet modules
Process stations and the operator and engineering
level in the Freelance 800F system communicate with
each other via Ethernet.
| Ethernet modules for the system bus |  |  |
| Type | Channels | Function |
| Ethernet module | 1 | Twisted pair connection 10 base T for connection to hubs or switches |
 |  |  |
| Ethernet module | 1 | BNC connection 10 base for thin coaxial cable (Cheapernet), 10 MBit/s |
 |  |  |
| Ethernet module | 1 | AUI connection 10 base 5 and 10 base FL via coupler |
 |  |  |